Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
7-22
RESET TO FACTORY
SETTINGS
This function resets all or a specific part of the holding registers to factory
settings.
NOTE!
It is recommended that a backup of the configuration is done before the
factory reset. Then the old transmitter configuration can be loaded if
necessary.
RRM: choose menu option Tools>Factory Settings:
Figure 7-17. The Reset to
Factory Settings window in
RRM.
AMS Suite: Tools/Service>Factory Settings.
HART Command: [3, 2, 1, 2].
DeltaV:
1. In the DeltaV Explorer, select the desired transmitter icon, and click the
right mouse button on the Transducer 1100 block icon:
2. Choose the Factory Settings option.
Factory Settings
TRANSDUCER1100