Reference Manual
00809-0100-4530, Rev BA
July 2009
5-47
Rosemount 5300 Series
HART MULTI-DROP
CONFIGURATION
The 5300 transmitter can be run in multidrop mode. In the multidrop mode
each transmitter has a unique HART address.
Figure 5-19. Multidrop
connection
The poll address can be changed by using a 375 Field Communicator or by
using the Rosemount Radar Master software.
To change the poll address using a 375 Field Communicator, choose HART
command [2, 2, 4, 1].
To change the poll address using the Rosemount Radar Master (RRM)
software:
1. Choose the Setup>General option.
2. Select the Communication tab.
3. Set the desired address (between 1 and 15 for multidrop operation).
4. Click the Store button to save the new address.