Instruction Manual
CI-9110
Mar. 2007
Series 9110
Remote Set Regulator
Model 9110-00A
Przeglądanie stron 0
1 2 3 4 5 6 ... 73 74

Podsumowanie treści

Strona 1 - Model 9110-00A

www.EmersonProcess.com/Bristol Instruction Manual CI-9110 Mar. 2007 Series 9110 Remote Set Regulator Model 9110-00A

Strona 2

0-2 / Contents 9110 Remote Set Regulator SECTION TITLE PAGE # Section 4 - FIELD WIRING (Continued) 4.3 ANALOG VOLTAGE INPUT (1-5 V) WITH

Strona 3 - REMEDIES

CI-9110 1-1 Introduction Chapter 1 INTRODUCTION 1.1 PRODUCT DESCRIPTION Series 9110-00A, Remote Set Regulators are transducer devices that use an e

Strona 4

Introduction 1-2 CI-5450 Figure 1-1 - Remote Set Regulator The CPU, clock and reset circuitry performs the timing, measurement and decision making

Strona 5

CI-9110 1-3 Introduction Figure 1-2 - Block Diagram of Analog Type Regulator

Strona 6 - Training

Introduction 1-4 CI-5450 The feedback pot connects across a regulated +5 Vdc source. The voltage at the feedback pot’s contact corresponds to the mec

Strona 7 - Help Files / Release Notes

CI-9110 1-5 Introduction Figure 1-3 - Block Diagram of Raise/Lower Type Regulator

Strona 8 - Training Courses

Introduction 1-6 CI-5450 1.2.4 Raise/Lower Regulator Model A block diagram for the Raise/Lower Regulator model is shown in Figure 1-3. It will be n

Strona 9 - TABLE OF CONTENTS

CI-9110 1-7 Introduction Table 1A - Model Number Breakdown (Continued) C = PNEUMATIC OUTPUT D = MOUNTING ARRANGEMENT 1 = 3-15 psi 1 = 2 In. P

Strona 11 - INTRODUCTION

CI-9110 2-1 Installation Chapter 2 INSTALLATION 2.1 GENERAL Proper installation techniques will ensure highest performance and also minimize measu

Strona 12 - Introduction 1-2 CI-5450

IMPORTANT! READ INSTRUCTIONS BEFORE STARTING! Be sure that these instructions are carefully read and understood before any operation is attemp

Strona 13 - CI-9110 1-3 Introduction

Installation 2-2 CI-9110 2.3 PRESSURE CONNECTIONS Remote Set Regulators are furnished in models that provide 3-15, 3-27 or 6-30 psig outputs. All m

Strona 14 - 1.2.3 Current Output

CI-9110 2-3 Installation shutoff valve allows the supply source to be closed down during maintenance checks without disturbing other equipment operati

Strona 15 - CI-9110 1-5 Introduction

Installation 2-4 CI-9110 2.3.3 Line Size For most installations 1/4 inch pipe or tubing is satisfactory. However, if the input or output lines run

Strona 16 - 1.3 DATA PLATE

CI-9110 2-5 Installation using a flat metal bar or similar tool. When replacing the cover, it should be snugged in and not over-tightened. The threads

Strona 17

BLANK PAGE

Strona 18 - BLANK PAGE

CI-9110 3-1 Board Setup Chapter 3 BOARD SETUP 3.1 USING OPTION SWITCHES Two switch assemblies (SW1 and SW2) are used to set options and select ran

Strona 19 - INSTALLATION

Board Setup 3-2 CI-9110 3.1.1 Switch Functions The Regulator assembly is configured by two, eight-switch packages which perform the functions list

Strona 20 - 2.3 PRESSURE CONNECTIONS

CI-9110 3-3 Board Setup 3.3.1 Continuous Signal A continuous input signal is one that, when placed in a TRUE state, will cause the output to change

Strona 21 - 2.3.2 Moisture in Lines

Board Setup 3-4 CI-9110 The relationship between an ON and OFF pulse time periods are shown by the following two equations: 1) T on Minimum (sec.)

Strona 22 - 2.4 INTERNAL ACCESS

CI-9110 3-5 Board Setup 3.5 GUARD INPUT The guard input (TB1-5 & TB1-6) is used to Enable or Inhibit the command input. This feature provides as

Strona 23 - CI-9110 2-5 Installation

WARRANTY A. Bristol warrants that goods described herein and manufactured by Bristol are free from defects in material and workmanship for one year

Strona 24

Board Setup 3-6 CI-9110 Table 3-3 - Switch SW2 (2-5), Output Rate Of Change SW2-5 SW2-4 SW2-3 SW2-2 Nominal Rate Of Change, ±15% Close Close Clo

Strona 25 - BOARD SETUP

CI-9110 3-7 Board Setup FAIL-ZERO MODE (Both Jumpers in B position) In the "B" position (if the Guard signal remains TRUE), a failure of

Strona 27 - 3.3.2 Incremental Signal

CI-9110 4-1 Field Wiring Chapter 4 FIELD WIRING 4.1 GENERAL This section illustrates and describes the field wiring terminals and various wiring co

Strona 28 - 3.4 INPUT FILTER

Field Wiring 4-2 CI-9110 Table 4-1 - Terminal Identification For Analog Input Models TERMINAL LEGEND FUNCTION TB1-1 TB1-2 TB1-3 TB1-4 TB1-5 TB1-

Strona 29 - 3.6 OUTPUT RATE OF CHANGE

CI-9110 4-3 Field Wiring Figure 4-2 - Analog Voltage Input with Guard Figure 4-3 - Analog Current Input with Guard

Strona 30 - Rate Of Change, ±15%

Field Wiring 4-4 CI-9110 For the application of Figure 4-2, the Carrier Presence output signal of the receiver may be connected to the Guard termina

Strona 31 - CI-9110 3-7 Board Setup

CI-9110 4-5 Field Wiring Figure 4-5 - Raise/Lower & Guard Inputs from Relay Contacts Figure 4-5 - Raise/Lower & Guard Inputs from Open C

Strona 32

Field Wiring 4-6 CI-9110 CAUTION When using the Regulator with a device that provides latching type outputs (output stays ON until turned OFF), the

Strona 33 - FIELD WIRING

CI-9110 4-7 Field Wiring Figure 4-7 - DC Supply Connections 4.8 OPERATING NOTES The startup procedures described herein are general for most appl

Strona 34

How to return material for Repair or Exchange Before a product can be returned to Bristol for repair, upgrade, exchange, or to verify proper operati

Strona 35 - CI-9110 4-3 Field Wiring

Field Wiring 4-8 CI-9110 5. If the output pressure of the Remote Set Regulator fails to change even with a change at the Command input, the intern

Strona 36 - Field Wiring 4-4 CI-9110

CI-9110 5-1 Service Chapter 5 SERVICE 5.1 GENERAL The servicing and calibration procedures described in this section should only be performed by

Strona 37 - CI-9110 4-5 Field Wiring

Service 5-2 CI-9110 5.2 TROUBLESHOOTING HINTS Some basic types of problems that can occur in the field are listed as follows: ○ Unit dead, no moto

Strona 38 - 4.7 DC POWER

CI-9110 5-3 Service 5.3 SETTING OUTPUT LIMITS 5.3.1 General Principles The Regulator provides mechanical output limits that prevent the output fr

Strona 39 - 4.9 INITIAL CHECKS

Service 5-4 CI-9110 8. Once limits have been set, re-apply dc power and adjust input test circuit (analog or raise/lower) for range value above upper

Strona 40 - Field Wiring 4-8 CI-9110

CI-9110 5-5 Service 5.6 PRELIMINARY CALIBRATION CHECK Once the test setup of Figure 5-2 or 5-3 has been completed, the following conditions must be

Strona 41 - SERVICE

Service 5-6 CI-9110 5. If above readings are within stated specifications, stop! No calibration is required. Restore instrument to normal operation.

Strona 42 - 5.2 TROUBLESHOOTING HINTS

CI-9110 5-7 Service 2. Reading on test gauge should be minimum range value (3 or 6 psi), ±5%. 3. Adjust input test circuit for 5.000 V. 4. Rea

Strona 43 - 5.3 SETTING OUTPUT LIMITS

Service 5-8 CI-9110 5. DMM #1 should read 4.995 V, ±.01 V 6. If the reading of step 5 is out of tolerance, adjust potentiometer R35 on CPU Board t

Strona 44 - 5.5 CALIBRATION PRECAUTION

CI-9110 5-9 Service Figure 5-4 - Assembly, Analog Type CPU Board with Current Output Figure 5-5 - Assembly, Analog Termination Board

Strona 45 - CI-9110 5-5 Service

Bristol Inc. Repair Authorization Form (off-line completion) (Providing this information will permit Bristol Inc. to effectively and efficiently proce

Strona 46 - Service 5-6 CI-9110

Service 5-10 CI-9110 Figure 5-6 - Assembly, Raise/Lower Type CPU Board with Current Output Figure 5-7 - Assembly, Raise/Lower Termination Board

Strona 47 - CI-9110 5-7 Service

CI-9110 6-1 Specifications Chapter 6 SPECIFICATIONS 6.1 ANALOG INPUT MODEL Function: Uses Analog Input to set a pressure output signal. Ranges:

Strona 48 - 5.9 PCB REFERENCE DRAWINGS

Specifications 6-2 CI-9110 6.3 GUARD INPUT Enables or inhibits command signal input on both Analog and raise/Lower models. 6.4 ANALOG OUTPUT Fun

Strona 49 - CI-9110 5-9 Service

CI-9110 6-3 Specifications Hysteresis: (Output to gauge) 0.5% of span Motor Protection: Adjustable mechanism limits restrict output for over and un

Strona 50 - Service 5-10 CI-9110

Specifications 6-4 CI-9110 Humidity: 10 to 95% over -20° to +130° F (-29° to +55° C) range 10 to 50% over +130° to +150° F (+55° to +65° C) rang

Strona 51 - SPECIFICATIONS

CI-9110 7-1 Parts Chapter 7 PARTS 7.1 MODEL 9110 MAIN PARTS Parts Referenced in Figure 7-1 Item Description Part Number 1 Housing 390

Strona 52 - Specifications 6-2 CI-9110

Parts 7-2 CI-9111 Figure 7-1 – Remote Set Regulator Actuator Unit

Strona 53 - 6.11 ENVIRONMENTAL

CI-9110 7-3 Parts Parts Referenced in Figure 7-1 (Continued) Item Description Part Number 45 Clamp, Sleeve 390102-01-6 50 #4 Cable Clip

Strona 54 - Specifications 6-4 CI-9110

Parts 7-4 CI-9111 7.2 REMOTE SET REGULATOR BASIC PARTS Parts Referenced in Figure 7-3 Item Description Part Number 103 Diaphragm 383825-

Strona 55 - Chapter 7

Supplement S1400 / 1Supplement S1400Guidelines forSystem Grounding- Contents -IMPORTANCE OF GOOD GROUNDS ... 1GENERAL RECO

Strona 56 - Parts 7-2 CI-9111

Bristol Training GET THE MOST FROM YOUR BRISTOL BABCOCK INSTRUMENT OR SYSTEM • Avoid Delays and problems in getting your system on-line • Minim

Strona 57 - CI-9110 7-3 Parts

2 / Supplement S1400BURRY TO DEPTH OF AT LEAST 3 FEET,DEEPER IN DRY SOIL.(b) INSTALL WITHOUT KINKS OR SHARP BENDS.(a) BRING ALL CONDUCTORS TO THE SU

Strona 58 - Parts 7-4 CI-9111

Supplement S1400 / 3GENERAL RECOMMENDATIONSWhen wiring equipment into a system, the electrical conduit must have a diameter that willaccommodate the d

Strona 59 - System Grounding

4 / Supplement S1400GROUND BEDCONDUCTORGROUNDING BUS1" COPPERRADIUS = 12 IN.AWG 4OR LARGERSTRANDED COPPER CABLEAWG 0000AWG 10COPPER WIRESMOOTHLYD

Strona 60 - 2 / Supplement S1400

Supplement S1400 / 5the equipment. Wiring from input signal circuits and power circuits should be separatedas much as possible to minimize noise and t

Strona 61 - GENERAL RECOMMENDATIONS

6 / Supplement S1400METER STANDCLAMP OR BRAZECLAMP (S)LIGHTNING &SURGE PROTECTOR#14 BARECOPPER GROUNDCONDUCTORSIGNALCABLECONDUITCLAMPRADIUS = 12 I

Strona 62 - 4 / Supplement S1400

Supplement S1400 / 7TYPES OF EARTH GROUNDSA common misconception of a ground is that it consists of nothing more than a metal pipe driveninto the soil

Strona 63 - TRANSIENTS AND INTERFERENCE

8 / Supplement S1400POWER COMPANY GROUNDAND GROUND RODSERVICETRANSFORMERGROUND BEDCONDUCTORTEST POWER COMPANYGROUND RODLIGHTNINGARRESTERSEACH PHASENOT

Strona 64 - 6 / Supplement S1400

Supplement S1400 / 9The ac power required to operate a system typically includes a service transformer located atthe street and a main breaker box and

Strona 65 - TYPES OF EARTH GROUNDS

10 / Supplement S1400increased noise pickup and signal offset errors. If more information is required on this subject,the reader should refer to the p

Strona 66 - 8 / Supplement S1400

Supplement S1400 / 11ConduitTrayPwr. GridGroundIsolatedTerminalPower Jumpersfor ground ref.See text.Conduit Pipe*CHASSIS24VRET W1*DPC 33XXMETEL CABINE

Strona 67 - SOIL CONDITIONS

A Few Words About Bristol Inc. For over 100 years, Bristol® has been providing innovative solutions for the measurement and control industry. Our pro

Strona 68

12 / Supplement S14001. Multi-Cabinet Instrument Grounding using Multiple Supplies. The instrument ground(24VRET terminal) of each DPC in a cabinet m

Strona 69 - Supplement S1400 / 11

Supplement S1400 / 13Equipment Ground Plate BondedTo Structural Steel By Welding,Brazing, Or Bolting Or WithAuxiliary Bond Strap.EquipmentGround Plate

Strona 70

14 / Supplement S1400 4. Setting DPC Power Jumpers. If the DPC is a Model 3335 or 3310, jumpers W1A and W1B onthe System Interconnect Board must be

Strona 72

Customer Instruction Manual CI-9110 Mar., 2007 Remote Set Regulator - Model 9110-00A The information in this document is subject to change with

Strona 73

For technical questions regarding ACCOL products, OpenBSI Utilities, UOI and all other software except for ControlWave and OpenEnterprise products, ca

Strona 74

9110 Remote Set Regulator Contents / 0-1CI-9110MODEL 9110-00A REMOTE SET REGULATORTABLE OF CONTENTSSECTION TITLE PAGE #Section 1 -INTRODUCTION1.1 PROD